Battery Controller
12.1V 0.0A 100%
DC Voltage
12.10V
Historic data
[Press Enter]
6 Historic data
The VE.Net Battery Controller will keep track of the following variables to enable you to get more
information on the state and the past use of the batteries. This data will be stored in volatile
memory, which means that every time the battery controller is disconnected from the batteries the
values will be reset. It is also possible to reset these values in the “Historic Data” menu.
6.1 Where to find the “Historic Data” menu
Step 1.) Press “Enter” to enter the Battery Controller menu.
Step 2.) Press “▼” to scroll through the menu until you see ‘Historic Data”.
Step 3.) Press “Enter” to enter the Historic data menu
Historic data recorded
Name Unit Description
Deepest discharge Ah The deepest discharge in Ah.
Depth last disch. Ah The depth of the last discharge in Ah. This value will be reset to 0 when the
State of Charge reaches 100% again.
Number of Cycles No. Every time the battery is discharged below 65% of its rated capacity and
charged back to at least 90%, one cycle is counted.
Average discharge Ah The average discharge over all the cycles counted
Full discharges No. The number of times the battery has been discharged to a 0% state of
charge.
Cumulative Ah Ah Records all the discharging amp hours. This value gives an indication of
the chemical change the battery has endured.
Last full charge Day Number of days ago that the battery was fully charged.
Minimum voltage Volt Lowest voltage measured since last reset. Can be used to check that the
batteries haven’t been over discharged.
Maximum voltage Volt Maximum voltage measured since last reset. Can be used to check for
faulty charges and alternators.